  • MAG4P

    4 Zone Fire Panel

    • 4 programmable zones
    • Active end of line monitoring and head removal
    • 30 fire detectors per zone
    • Unlimited number of call points per zone
    • Integral evacuate alarm button
    • 'Class change' facility
    • Enable/disable security key
    • One man walk test facility
    • Volt free fire change over relay
    • Volt free fault change over relay
    • Individual sounder circuit fault ID
    • Individual zone/sounder isolate
    • CE certified to EN54 P2/4
    • Requires only 1x12v battery
    • MAG4P - ABS casing

Technical Specifications

Inputs
Max Detectors per Zone30
Thresholds for Zone Conditions0 - 2 mA (Fault condition) 2 - 6 mA (Normal condition) 6 - 110 mA (Fire condition) 110 mA - Short (Fault condition)
Power
Mains Fail Consumption 50mA
Mains Supply230 VAC ± 10%
Standby Supply1 x 7ah 12V S.L.A. Battery
Power Availability0.7 amps
Outputs
On Board Sounder Circuits (4)300mA @ 24V fuse resettable (PTC)
Sounder Expander Cards (4)150mA @ 24V fuse resettable (PTC)
Fault/Fire RelayVolt free 500mA @ 24V (max load)
Auxiliary Output24VDC (300mA fused)
Environment
Working Temperature0 to 40ºC
Storage Temperature-20 to 60ºC
Humidity0 to 93%
Dimensions (mm)456 x 350 x 125mm