MAG8 Fire Panel Instruction Manual

 
MAG8
4 Zone Fire Panel expandable to 8 zones

  • 4 programmable zones

  • Expandable to 8 zones VIA MAGZC

  • Activate end of line monitoring

  • 30 fire detectors per zone

  • Unlimited number of call points per zone

  • Integral manual alarm button

  • Repeater facility

  • Zone operated relay facility

  • 'Class change' facility

  • Enable/disable security key

  • One man walk test facility

  • Fire volt free change over relay

  • Fault volt free change over relay

  • Individual sounder circuit fault ID

  • Individual zone/sounder isolate

  • Alarm delay options

  • BS5839 and EN54 compliant

  • CE certified

  • Requires only 2x12v batteries

  • Metal casing

 

 

The MAG Fire Alarm Centre has been carefully designed to answer the rigorous demands of specifiers, installers and users. For specifiers, the MAG Alarm Centre offers a host of features, designed into a quality engineered package.
For installers, the MAG range is simplicity itself to install, program and expand. For users, the MAG Alarm Centre's confusion free instructions are clear and easy to understand and follow. Quality Reliability and Performance are the key words synonymous with the MAG Alarm Centre range.

 

 INPUTS  Max detectors per zone  30
   Thresholds for zone conditions  0-2 mA (Fault condition)
 2-6 mA (Normal condition)
 6-110 mA (Fire condition)
 110 mA + Short (Short condition)
 POWER  Mains fail consumption  85mA
   Mains Supply  230 VAC ± 10%
   Standby supply  2 x 7ah 12V S.L.A. Batteries
   Power availability  0.7 amps
 OUTPUTS  Sounder 1  24V (max 500mA fused)
   Sounder 2  24V (max 500mA fused)
   Fault Relay  Volt free 500mA (maximum load)
   Auxiliary output  24VDC (500mA fused)
 ENVIRONMENT  Working Temperature  0 to 40°C
   Storage Temperature  -20 to 60°C
   Humidity  0-95%
   Dimensions (mm)  350W 370H 100D
   Weight  6.2 KG