MAG4P Fire Panel Instruction Manual

 
MAG4P
4 Zone Fire Panel

  • 4 programmable zones

  • Activate end of line monitoring

  • 30 fire detectors per zone

  • Unlimited number of call points per zone

  • Integral manual alarm button

  • 'Class change' facility

  • Enable/disable security key

  • One man walk test facility

  • Fire volt free change over relay

  • Fault volt free change over relay

  • Individual sounder circuit fault ID

  • Individual zone/sounder isolate

  • BS5839 and EN54 compliant

  • CE certified

  • Requires only 1x12v battery

  • ABS casing

 

 

 

 INPUTS  Max detectors per zone  30
   Thresholds for zone conditions  0-2 mA (Fault condition)
 2-6 mA (Normal condition)
 6-110 mA (Fire condition)
 110 mA Short (Short condition)
 POWER  Mains fail consumption  50mA
   Mains Supply  230 VAC ± 10%
   Standby supply  1 x 7ah 12V S.L.A. Battery
   Power availability  0.7 amps
 OUTPUTS  Sounder 1  24V (max 300mA fused)
   Sounder 2  24V (max 300mA fused)
   Fault Relay  Volt free 500mA (maximum load)
   Auxiliary output  24VDC (300mA fused)
 ENVIRONMENT  Working Temperature  0 to 40°C
   Storage Temperature  -20 to 60°C
   Humidity  0-95%
   Dimensions (mm)  340W 290H 100D
   Weight  2.5 KG