MAG2 Fire Panel Instruction Manual

 
MAG2
2 Zone Fire Panel


  • 2 programmable zones

  • Activate end of line monitoring

  • 30 fire detectors per zone

  • Unlimited number of call points per zone

  • Integral manual alarm button

  • 'Class change' facility

  • Enable/disable security key

  • one man walk test facility

  • Fire volt free change over relay

  • Fault volt free change over relay

  • Individual sounder circuit fault ID

  • Individual zone/sounder isolate

  • BS5839 and EN54 compliant

  • CE certified

  • Requires only 1x12v battery

  • Metal casing

 

 

The MAG Fire Alarm Centre has been carefully designed to answer the rigorous demands of specifiers, installers and users. For specifiers, the MAG Alarm Centre offers a host of features, designed into a quality engineered package.
For installers, the MAG range is simplicity itself to install, program and expand. For users, the MAG Alarm Centre's confusion free instructions are clear and easy to understand and follow. Quality Reliability and Performance are the key words synonymous with the MAG Alarm Centre range.

 

 INPUTS  Max detectors per zone  30
   Thresholds for zone conditions  0-2 mA (Fault condition)
 2-6 mA (Normal condition)
 6-110 mA (Fire condition)
 110 mA Short (Short condition)
 POWER  Mains fail consumption  50mA
   Mains Supply  230 VAC ± 10%
   Standby supply  1 x 7ah 12V S.L.A. Battery
   Power availability  0.7 amps
 OUTPUTS  Sounder 1  24V (max 300mA fused)
   Sounder 2  24V (max 300mA fused)
   Fault Relay  Volt free 500mA (maximum load)
   Auxiliary output  24VDC (300mA fused)
 ENVIRONMENT  Working Temperature  0 to 40°C
   Storage Temperature  -20 to 60°C
   Humidity  0-95%
   Dimensions (mm)  200W 290H 80D
   Weight  2.7 KG